ARTICLE 445. GENERATORS
ARTICLE 445. GENERATORS445.11. Marking. Generators must be marked with the manufacturer's name, the frequency and number of phases for ac units, the output rating in kilowatts or kilovolt-amps, the corresponding normal volts and amperes, the rated RPM, and the rated ambient temperature or temperature rise, along with the power factor. In addition, generators over 15 kW must have the reactances (transient, synchronous, and subtransient, along with zero sequence), the power rating category, and the insulation class marked as well. Inverter-based generators need the maximum short-circuit current provided, in place of all the reactances except the zero sequence number. The nameplate must also stipulate how the generator is protected against overload, whether by…