ARTICLE 354. NONMETALLIC UNDERGROUND CONDUIT WITH CONDUCTORS: TYPE NUCCThis is the same product as Type HDPE conduit, and it follows the same installation rules, but conductors are preinstalled and shipped with the product by the manufacturer. Note that even though conductors arrive with the product preinstalled, it is still classified as a raceway, and the 360° maximum bends-in-the-run rule continues to apply. In this form, the upper size limit is metric designator 103 (trade size 4) conduit, also using the special bend radius Table 354.24.